920 Series RTD Transmitter
920_Prog Txr Software
User’s Manual
www.noshok.com
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - 920 Series RTD Transmitter

920 Series RTD Transmitter920_Prog Txr SoftwareUser’s Manualwww.noshok.com

Page 2 - Table of Contents

10“One Point” Calibration The “One point” calibration allows the user to offset the output of the RTD Transmitter to match perfectly a kn

Page 3

point must be at a higher value than the “First Point”. Once the output reading from the RTD Transmitter is stable, enter the temperature valu

Page 4

Corporate Headquarters1010West Bagley Road , Berea,Ohio 44017Ph: 440.243.0888Fax: 440.243.3472E-mail: [email protected]: www.noshok.comUM920

Page 5

2920_Prog Txr User’s Manual – Preliminary Version Table of Contents System Requirements ...

Page 6

3System Requirements To install the 920_Prog Txr Software, you need these minimum system requirements: • Pentium III – 600 MHz or better • 10 MB o

Page 7

4Reading Device By launching the 920_Prog Txr Software, the main window of the 920_Prog Txr software will appear on the screen (Figure #1).

Page 8

5The communication ports available on the computer can be seen in the Device Manager of Windows. The USB driver automatically creates a virtual

Page 9

6Calibration Date: To modify the last calibration date value, simply enter the new date in the text boxes called “Calibration Date”. The date has

Page 10 - 920_Prog Txr

7Filtering: The filtering option allows the user to set the time response of the digital filter implemented in the RTD Transmitter . The

Page 11

8To re-scale the RTD Transmitter in a range that is not included in the “Preset Range”, simply enter the value, in the current engineeri

Page 12 - Corporate Headquarters

9The next step is the adjustment of the 20 mA. To perform that operation, simply click on the 20 mA button located in the CURRENT ADJUSTMENT s